Installer Mode Programming i-on40
Page 14
to set or unset the system.
2. When the user operates the keyswitch while the
system is unset then the control unit starts the
programmed exit mode.
3. When the user operates the keyswitch while the
system is set then the control unit unsets the system
immediately.
4. The user cannot reset the system from a
Keyswitch zone.
5. Do not assign more than one Latched Key Switch
zone to a partition.
Tamper (10)
Use this zone type to monitor the tamper status of
external equipment. The control unit monitors a
Tamper zone at all times. When triggered in the
unset condition, only internal sounders operate.
When triggered in the set condition, the alarm
response determines whether external sounders,
strobe and communications also respond to the
alarm.
External PSU A/C Fail (11)
Use this zone type to monitor the A/C Fail output of
an external power supply unit. If a power supply unit
triggers a zone with this type then the control unit
waits for a random time between 52 and 59 minutes
before activating any output programmed as “AC Fail”
and causes an alert that displays “External mains fail”
on the keypad.
If the alarm system is set then the control unit logs
the event, starts any programmed communication,
but does not start an alarm.
External PSU Battery Fault (12)
Use this zone type to monitor the Battery Fault
output of an external power supply unit. If an
external PSU triggers a zone with this type then the
control unit activates any output programmed as
“Battery Fault” and causes an alert that displays
“External Battery Fault” on the keypad.