Installer Menu Options i-on160
Page 50
Type: Active when: Assign to
Partitions?
PIR Set Latch
(25)
The system or partition is set. Inactive
when the system or partition is unset or an
alarm condition occurs. The output is
active for one second when a reset is
performed or when the control unit leaves
installer mode.
Yes
Shock Sensor
Reset (26)
Exit time starts. The output remains active
for five seconds. Use this output to reset
shock sensors (for example, the "Viper").
Yes
Walk Test (27) A user starts Installer- or User Walk Tests.
Also active during the time between
silencing and resetting the system. This
output can be used on movement
detectors that are able to switch off the
Walk Test lamp in any state other than a
Walk Test.
No
Smoke Sensor
Reset (28)
This output is active (0V) all the time
except when a user acknowledges a fire
alarm: after which the control unit
deactivates the output for three seconds.
This output type is designed to be
connected to low-voltage smoke detector
reset terminals.
Yes
24 Hour Alarm
(29)
The control unit starts a 24 hour alarm. Yes
Settin
Complete (30)
The control unit finishes settin
. Active for
10 seconds.
Yes
Unset Complete
(31)
Someone unsets the system or disarms it
after an alarm. The output is active for 10
seconds.
Yes
Full Set Ready
(32)
None of the detectors are reportin
“alarm”
signals.
Yes (all
partitions by
default)
Full Set (33) The system is full set. If the system is
partitioned, then the output is active only
when all assigned partitions are Full Set.
Yes
Part Set (34) The system is part set. Yes
Part Set B (35) Setting Part Set B. Deactivated on
unsetting Part Set B. (Available only in a
Part Setting system)
No
Part Set C (36) Settin
Part Set C. Deactivated on
unsetting Part Set C. (Available only in a
Part Setting system)
No