4. Programming
Page 82 496964
In a partitioned system, the options are:
Option
0 Timed. Use this option if Partition B sets after an exit time selected
using Command 65. If an Exit Terminate button is fitted, the user may
use it to shorten the exit time.
1 Terminate. Use this option if the user completes setting the partition
by pushing an Exit Terminate button connected to a keypad. The exit
time is infinite in this option.
2 Final Door Set. Use this option to complete setting the partition by
closing a door fitted with a Final Exit zone detector. The exit time is
infinite in this option.
3 Instant Set (no exit tone)
4 Silent Set. Use Command 65 to program the Exit time. At the end of
the exit time the keypad gives a double "beep" confirmation tone.
5 Lock Set. See "Level A Exit Mode (Command 39) for an explanation
of Lock Set.
Note: The keypads give a double "beep" confirmation tone at the end of all
setting modes.
63: Level/Partition B Alarm Response
This Command sets the alarm response for Level or Partition B.
In a single system, the options are:
Option
0 Keypad sounders only.
1 Internal sounders and keypad sounders.
2 Local alarm (internal and external sounder only).
3 Full alarm (communication and internal/external sounders).
In a partitioned system, the options are:
Option
0 Keypad sounders only.
1 Local alarm (internal and external sounder only).
2 Full alarm (communication and internal/external sounders).
64: Level B Entry Time
This Command has been replaced by Command 202.