4. Programming
Page 48 496964
Summary of Programming Commands
Command Key in:
0 Country PTT Defaults (page 61)
0Y
nY
n = Country:
0 = UK Y
1 = Italy (I)
2 = Spain (EE)
3 = Portugal (P)
4 = Netherlands (NL)
5 = France (FR)
6 = Belgium (B)
7 = Germany (D)
8 = Switzerland (CH)
9 = Austria (A)
X1 = Ireland (IRL)
X2 = OEM 1
X3 = OEM 2
X4 = Finland (FI)
X5 = Norway (N)
X6 = Denmark (DK)
X7 = Sweden (S)
Note: Executing this Command loads
all defaults for the selected country.
Command Key in:
01–X40
Zone Programming (page 61)
nnYYab
nn = Zone number:
01 to 24 for 9751
01 to 32 for 9752
01 to 40 for 9851
Note:
For zones 1 to 16, key in "01" to "16"
For zones 17 to 40, key in "X17" to
"X40"
a = Zone type, one of:
00 = NU (Not Used)
01 = PA (Panic Alarm)
02 = FR (Fire)
03 = NA (Normal Alarm)
04 = 24 (24-hour)
05 = FE (Final Exit) see X7 below
06 = ER (Entry Route) see X7 below
07 = SA (Shock Analyser) see X7 below
08 = TC (Technical Alarm)
09 = KB (Keybox)
10 = SD (Smoke Detector)
11 = KM (Keyswitch Momentary)
12 = KF (Keyswitch Fixed)
13 = AM (Anti-Mask)
14 = FB (Forbikobler) see X7 below
b = Zone attributes, any of:
X1 = C (Chime)
X2 = S (14-day Soak Test)
X3 = D (Double Knock)
X4 = O (Omit Allowed)
X7 = 1–6 or 1–4
For zone type 07, shock analyser
sensitivity: 1 (low) to 6 (high)
For zone types 05, 06 and 14,
entry timer number: 1 to 4 (see
Commands 201–4 on page 116)
A = a (armed in Level/Partition A)
B = b (armed in Level/Partition B)
C = c (armed in Level/Partition C)
D = d (armed in Level/Partition D)
Default zone types for a
single system:
Default zone types in a
partitioned system:
Z01=FE abcd 1 Z01=FEa 1
Z02=ER abcd 1 Z02=ERa 1
Z03-Z07=NA abcd Z03-07=NA a
Z08=PA abcd Z08=PA a
Z09-Z40=NU a
Example: To set Zone 17 as a Normal
Alarm, active in Level B and with Omit
Allowed. Key in:
X17YY Zone Number
03 Normal Alarm
B Active in Level B
X4 Omit Allowed
Y to store the value of the Command