4. Programming
496964 Page 97
108: Dynamic Test Call
With dynamic testing, the control unit makes a test call 24 hours after the last
communication, rather than at the fixed times or intervals specified for static
calls with Command 105 (page 95). Select option 0 to disable dynamic test
calls and option 1 to enable dynamic test calls.
Note: Cooper Security recommends that you select either Static Test Call
(105) or Dynamic Test Call (108), but not both at the same time.
109: Three-way Calling (UK only)
To use three-way calling, you must make sure that the BT Network Services
Option of "three-way calling" is available on the telephone line to which the
communicator is connected.
Option
0 Three-way calling off. This mode is disabled.
1 Three-way calling on. This mode is enabled.
Operation: If the communicator, when triggered by the control unit,
detects Off Hook or Incoming Ringing, it sends an 80ms trigger. This
trigger represents the "R" or Recall button on a telephone and is
interpreted by the exchange as a request for a new clean line. When
the new line is available, the communicator tries to connect to the
programmed receiver number.
110: Download Mode
You can program the control unit from a PC using Downloader software. The
PC can be connected to the control unit using the telephone network or, for
the 9752 or 9851 model, locally using a cable. This Command enables you to
select one of these options.
Option (not 9751)
0 Local. Programs the control unit for a cable connection.
1 Remote. Programs the control unit for a telephone connection, in
which case it will wait for and answer a call from the remote PC. You
will need to use Commands 112 and 113 to configure the connection.
Notes:
1. There is no option for this command on the 9751, which has no
connector for a local PC: 110
Y
selects Remote.
2. Secure Callback does not work with this Command.
3. The control unit will exit from this Command if Downloader does not call
within 30 minutes.