Engineer Menu 1-2 Engineering Manual
32
Option 1-2: Choosing Advanced Zone Options
Resistance 1
4K7 / 2K2
e.g.
|
Panel Zone 1
0001 Normal Alm
Resistance 2
1K0 / 1K0
Set Output Group
Output Group >--
Set Output Group
Output Group >01
Panel Zone 2
0002 Entry
[
|
[
[
|
e.g.
2 . SEL EC T ZON E
RESI STANCE
3. SELECT ZO N E'S
OUTPUT GROUP
[
Eng 1 Menu 2
Zones Advanced
1. SELECT ZONE
e.g.
Lo c a t i o n
Zo n e t y p e (se t
up in Eng 1-1)
Zo n e
To se le c t zo ne :
Pr e s s
Pr e ss o r t o sc r o l l , o r
to choose zone on next network
(e.g. to change 0001 to 1001), or
Enter zone number (e.g. 0002)
|¬
r
To se le c t zo n e re sist a n c e s:
Pr e s s o r
|¬
to sc roll, o r
Press the hot key (1-4)
Pre ss to sa ve c ha ng e s a nd c o n t inue
[
To select zone output group:
Pr e s s o r
|¬
to sc roll, o r
Enter group number (e.g. 04)
Pre ss to sa ve c ha ng e s a nd c o n t inue
[
This option enables you to select the resistance values used at the sensor, and to create output
groups.
Step 1 – Select Zone Number
Choose the zone you want to set up by selecting its zone number (see page 21 for further
details).
Step 2 – Select Zone Resistance
Select the resistance values used at the zone sensor. The first value is the alarm shunt resistance,
and the second is the end-of-line resistance. If you are using a zone with masking (page 26),
select 4K7/2K2.
This option is relevant only if the zone sensor is connected using the fully-supervised loop
connection method, as described in the
Installation Instructions
. If the zone sensor is connected
using closed circuit wiring then leave the option set to 4k7/2k2.